9000m3 Dehumidifier
| Condition:New | Place of Origin:China (Mainland) | Brand Name:TH | Model Number:TZH-Y/G-F-18/DD |
| Voltage:380V/415V/3Ph 50Hz | Dimension(L*W*H):4300 * 2300 * 3150 (mm) | Weight:7.9 tons | Certification:ISO |
| Warranty:12 months | After-sales Service Provided:Overseas third-party support available |

Main technical parameters
| Equipment Model | TZH-Y/G-F-9/DD |
| Electrical power | 3ph, 380V/415V/50Hz |
| Main control procedure | 100% refrigerating / 100% Desiccant rotor / Refrigerating + Desiccant rotor / 100% heating |
| Dehumidifying air volume | 9000m3/h |
| Desiccant rotor dehumidifying air volume | 9000m3/h |
| Regeneration air volume | 3000m3/h |
| Desiccant rotor | Imported from Japan NICHIAS desiccant rotor, honeycomb structure, desiccant agent silica gel, washable, service life≥15years |
| Extra pressure of exhaust air | ≥1800 Pa |
| Refrigerating output | 323.8kw×846.21=274000Kcal/h |
| Compressor | Germany BITZER screw compressor |
| Condenser cooling type | Air cooling |
| Refrigerant | R22 (update available) |
| Heating type | Electrical heating |
| Temperature control type | High sensitive temperature sensor +PLC auto control +Touch Screen |
| Air inlet condition | Winter: Temperature≥-10°C, RH≤95% Spring & Autumn: Temperature15~20°C, RH≤95% Summer: Temperature≤40°C,RH≤95% |
| Air outlet condition | Winter: Temperature≥25±3°C, RH≤45% Spring & Autumn: Temperature≤25±3°C, RH≤45% Summer: Temperature≤25±3°C,RH≤45% |
| Evaporator | Copper tube + hydrophilic aluminum fins Size of copper tube Ø12.7×0.5mm |
| Condenser | Copper tube + hydrophilic aluminum fins Size of copper tube Ø9.52×0.5mm |
| Structure of equipment | Container structure as one whole |
| Size of air outlet | 600×600 with switch valve and connection joint |
| Electrical control cabinet | PLC control IP54 sealant + protection of electrical linkage, phase default, high and low voltage, overload + air pressure exceeding protection Protection for electric and pneumatic separately Self-diagnosis |
| Temperature & humidity control and display | Refrigerating + Desiccant rotor regeneration heating Temperature + electrical heating |
| Fault display | Phase sequence protection / compressor fault / desiccant rotor fault / overload display / air pressure exceeding / no air flow in ducting alarming / overheating of electrical heater alarming etc. |
| Pressure display and protection | High, low pressure display + Protection |
| Air inlet filtering | Efficiency 93% / Washable double layer filtering / frame material aluminum alloy / filtering precision 0.5μm |
| Weight | 7.9 tons |
| Max outsize | L×W×H: 4300mm×2300mm×3150mm |
| Premier paint & film thickness | 2×100μm Paint: epoxy Color: Ocean blue |
| Finish paint & film thickness | 2×75μm Paint: epoxy Color: Ocean blue |

| Packaging Detail:In container |
| Delivery Detail:7 workdays after recieved your down payment |