Item | Item Description |
Input | Rated Voltage and Frequency | Single/Three phase 220VAC,three phase 380VAC,50/60Hz |
| Allowable Voltage Range | Voltage fluctuation range: +10%,-15% frequency fluctuation±5% |
Output | Rated voltage | Three-phase:0~input voltage |
| Frequency | 0.10~400.00Hz |
Overload capacity | Type G:150% 1minute, Type P:120% 1minute |
Control Function | Control Method | SPWM |
| Control Mode | V/F Control/Current Vector Control |
| Torque Feature | With torque compensation and slip compensation, start torque can reach 150% at 1.0Hz |
| Frequency Control Range | 0.1~400Hz |
| Frequency Accuracy | Digital setting: Max. frequency x ±0.01%(-10°C~+40°C) Analog setting: Max. frequency x ±0.2%Hz (25°C±10%) |
| Frequency Resolution | Digital setting:0.01Hz; Analog setting: Max. frequency x 0.1% |
| Output Resolution | 0.01Hz |
| Frequency Setting Signal | 0~10V(20kΩ),0~20mA(250Ω),4~20mA(250Ω) |
| Acceleration/Deceleration | 0.0~3600.0 sec/min, which can be set in sequence. |
Performance | Braking Torque | About 20% without braking resistor, and about 125% with braking resistor |
| V/F Mode Classes | 12 preset V/F mode and programmable V/F mode |
| Instantaneous Over Current | General Mode(G):About 250% AC motor driver rated current Blower/Pump Mode(P):About 200% AC motor driver rated current |
| Over Load | General Mode(G):150% rated output current for 1 minute before sliding stop Blower/Pump Mode(P):120% rated output current for 1 minute before sliding stop |
| Over Voltage | Motor stops sliding when rectifier output voltage exceeds 410V(200V class)/820V(400V class) |
| Under Voltage | Motor stops sliding when rectifier output voltage drops down to 190V(200V class)/380V(400V) or lower |
| Instantaneous Power-Failure Compensation | Instant stop when instantaneous power-failure lasts for 15ms or longer.(Default setting) According to standard setting, if the power –failure is shorter than 2 seconds, continue operation. |
| Heat Sink Overheat | Thermistor protection, takes effect when temperature exceeds 105Ω |
| Speed Loss Protection | Speed loss protection during acceleration, deceleration and constant speed operation |
| Grounding Failure | Electronic circuit protection, takes when leakage current reaches 50% of AC motor driver rated current. |
Environment | Environment Temperature/Humidity | -10°C~+40°C, 90%RH and lower (no dewing) |
| Operation Location | Altitude below 1000M,indoor use(no corrosive gas, liquid, no dust) |
| Storage Temperature | -20°C~60°C |
| Vibration | Below 20Hz 9.8m/s2(1G) , 20~50Hz 5.88m/s2(0.6G) |