50kW 60kW Air to water chiller

Model KLS-50J2 KLS-60J2,KLS-50J2 KLS-60J2 Industrial Air Conditioners Zhejiang,China(Mainland) Ref 10243123

Price on request

Pricing is provided on request — use the quote form below.

Port
Shanghai,Ningbo
Minimum Order Quantity
1 Unit/Units
Supply Ability
500 Unit/Units per Month
Payment Terms
L/C,T/T

Request a Quote

Product: 50kW 60kW Air to water chiller

Attachment optional · PDF, Word, Excel, image · max 10 MB
No file chosen
We usually reply within 12 hours.

Key features

Applied range:Room cooling or industry cooling·Electronic expansion valve·Wire controller·Galvanized plate shell

Specifications

Type Chiller,Air Source Heat Pump Place of Origin ZHE,Zhejiang, China China (Mainland)
Model Number KLS-50J2 KLS-60J2,KLS-50J2 KLS-60J2 Operating Voltage 380/400 VAC
Mounting Floor Standing Certification CE
Installation Freestanding Color White
Details Applied range:Room cooling or industry cooling · Electronic expansion valve · Wire controller · Galvanized plate shell

Packaging & delivery

Packaging DetailPlywood base.5 units per 20ft container.11 units per 40ft container.
Delivery Detailwithin 25 days

Product description

Product Features:


2.Eco-friendly refrigerant: R407C.
3.Electronic expansion valve regulates the flow of refrigerant precisely.
4.Air exchanger(Fins-coil) with hydrophilic coating.
5.Galvanized plate shell, powder coating.
6.LCD display wire controller.
7.Can set the operating time freely.
8.Unit runs or stop automatically according to water return temperature.
9.Compatibility of indoor signal control(10~12V).
10.Water flow protection control.
11.Failure diagnosing function.
12.Modular design,units combine freely.

Technical Specifications:

ModelKLS-50J2KLS-60J2
Power supply(V/Ph/Hz)380-415/3/50
CoolingCooling capacitykW5060
Rated power inputkW17.621
EERW/W2.82.8
Circulating water flowm3/h8.810.5
Water resistancekPa≤45
Compressor typeScroll
RefrigerantR407C
NoisedB(A)6666
Net weightkg700830
Unit dimensions(L×W×H)mm2025×1030×1995
Packing dimensions(L×W×H)mm2130×1075×2080
Stacking layerslayer11
Water pipe connectormmDN65(2-1/2")
Ambient condition°C-10~43
Water side exchangerShell&tubeShell&tube
Water flow switchbuilt inbuilt in
1)Cooling rated test conditions:Ambient temp.(DB/WB): 35°C/24°C,Water temp.(In/Out):12°C/7°C.
Remarks:
Fexible range with other refrigerants (e.g. R22), other various power supply available according to the client's requirement.

FAQ

What model is this machine?
The model number is KLS-50J2 KLS-60J2,KLS-50J2 KLS-60J2.
What type of machine is it?
It is a Chiller,Air Source Heat Pump.
What certifications does it have?
Certification: CE.

Related products in Industrial Air Conditioners