400W IP23/IP55 energy-saving industrial cabinet air conditioning unit

Model SAD104-1 Industrial Air Conditioners Jiangsu,China(Mainland) Ref 10222626

Price on request

Pricing is provided on request — use the quote form below.

Port
SHANG HAI
Minimum Order Quantity
50 Piece/Pieces
Supply Ability
2000 Piece/Pieces per Month
Payment Terms
T/T

Request a Quote

Product: 400W IP23/IP55 energy-saving industrial cabinet air conditioning unit

Attachment optional · PDF, Word, Excel, image · max 10 MB
No file chosen
We usually reply within 12 hours.

Key features

cabinet air conditioner·1.Long service life·2.High stability and efficiency·3.Competitive price

Specifications

Condition New Type Cabinet Air Conditioner
Place of Origin Jiangsu China (Mainland) Model Number SAD104-1
Operating Voltage 220VAC Mounting door mount
Certification CE After-sales Service Provided Engineers available to service machinery overseas
Rated Voltage 220VACd15% 50/60Hz Cooling Working Temperature +20~+55 Degrees Celsius
Heating Working Temperature -40~+15 Degrees Celsius Cooling Capacity 400W
Refrigerant R134a Weight 18.5 Kgs
Noise 62dB Color RAL7035
IP Grade IP23/IP55 Dimension(W*H*D) 470*788*185mm
Details cabinet air conditioner · 1.Long service life · 2.High stability and efficiency · 3.Competitive price

Packaging & delivery

Packaging Detail1 PC/Carton with foam
Delivery Detail25 Days After Deposit or L/C

Product description

Door Mounting Cabinet Air Conditioner

Scope:

1.Widely used in telecommunications,broadcasting,electricity,automation and other industries outdoor cabinet,IDC room cooling needs.

2.Applications:electric equipment control box,battery compartment,and telecommunication equipment and other pertinent equipments,enclosed area climate control such as wireless communication cabinet,battery cabinet,industry control cabinet etc.

Features:

1.Applicable for severe ambient environment,such as high temperature.

2.Can work perfectly from -40 to +55 Degrees Celsius.

3.Using natural cooling technologies,energy efficient operation.

4.Keep dust,oil fog and moisture from entering the internal of the equipments.Totally solve dust and moisture contamination issues caused by ventilation.

5.Flexible installation,can be installed perfectly in the side or outside wall of the equipment.

Technique Data Sheet:

Installation Instruction:

1.Don't use the equipment in the environments with more dust, oil moisture, corrosive or harsh air. Among them shall not exceed 55°C ambient temperature, and not lower than 0°C, humidity should not exceed 95%.

2.Use M6*10 screws fix flange on cabinet.

3.Drain cannot stress, after the installation must ensure smooth condensate drain,handling or moving the equipment,do not upside down, tilt and collision.

Installation Picture:

Application:

Related Products:

How to Determine Correct Model of Cabinet cooler

Key Point---Calculating Heat Load for your Enclosure
To determine the correct model for your application, it is first necessary to determine thetotal heat loadto which the control panel is subjected. This total heat load is the combination of two factors — heat dissipated within the enclosure and heat transfer from outside into the enclosure.

Steps of Calculating Btu/hr.:
1. First, determine the approximate watts of heat generated within the enclosure.Watts x 3.41 = Btu/hr.

2. Then, calculate outside heat transfer as follows:
a. Determine the area in square feet exposed to the air,ignoring the top of the cabinet.
b. Determine the temperature differential between maximum surrounding temperature and desired internal temperature. Then, using the Temperature Conversion Table (below), determine the Btu/hr./ft.2for that differential. Multiplying the cabinet surface area times Btu/hr./ft.2provides external heat transfer in Btu/hr.

3. Add internal and external heat loads to get total heat load.

Temperature Conversion Table

Temperature
Differential ° F
Btu/hr/ft.2
51.5
103.3
155.1
207.1
259.1
3011.3
3513.8
4016.2
Example:
Internal heat dissipation: 650 Watts or 2216 Btu/hr.
Cabinet area: 40 ft.2
Maximum outside temperature: 110°F
Desired internal temperature: 95°F
The conversion table (above) shows that a 15°F temperature differential inputs 5.1 Btu/hr./ft.2

40 sq. ft. x 5.1 Btu/hr./ft.2= 204 Btu/hr. external heat load.

Therefore, 204 Btu/hr. external heat load plus 2216 Btu/hr. internal heat load = 2420 Btu/hr. total heat load or Btu/hr. refrigeration required to maintain desired temperature.
In this example, the correct choice is a 2500 Btu/hr. Cabinet Cooler System.

More details,contact us!

FAQ

What model is this machine?
The model number is SAD104-1.
What type of machine is it?
It is a Cabinet Air Conditioner.
Is it new or used?
Condition: New.
What voltage does it operate on?
Operating voltage: 220VACd15% 50/60Hz.
How much does it weigh?
Weight: 18.5 Kgs.
What certifications does it have?
Certification: CE.
What warranty is offered?
Warranty: Engineers available to service machinery overseas.